{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

Can I use only one push button without password to reset the latches?

Yes, by using one of the F buttons. In function buttons menu, define F1 “Selected control” F1 and give a pulse time, e.g. 1s. In “Release latches” menu define “DI to release latches” as F1. Alternatively, you can use F2.

施耐德電機Taiwan

探索更多
系列:
Easergy P3 Protection Relays
探索更多
系列:
Easergy P3 Protection Relays