我们今天能为您提供什么帮助?
How can I change setting group when using IEC61850 on Easergy P3 Relay
By writing “True” to one of Logical Nodes SG1GGIO135, SG2GGIO136 and SG3GGIO135 SG4GGIO135. E.g. SG1GGIO135 will set all protection stages to group 1.