我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Details of 300 Hz Leakage current presence in the Variable speed drives (VSD).
Leakage current is caused by:
- "not-ideal" parameters of every insulation laying between living parts and ground
- components connected between living part (any phase) and ground by purpose, for example overvoltage protection, EMC filter, etc.

When speaking about VSD,, the leakage current has 2 parts:
1. Due to built-in EMC filter that is connected to the ground via capacitance, there is permanent constant part of leakage current at the same frequency as supply network. (50 or 60Hz). Note that built - in EMC filter can be disconnected from ground, which is especially required in IT networks
2. Due to ATV operation principle when potential on living parts (DC+, DC-, motor phases U.V,W) is permanently changed with high rise and fall (high dv/dt), there is current flown to the ground via stray capacitance. ic=C*dv/dt. Almost all ATVs have 3-phase input rectifier (also called 6-pulse bridge) which means that DC bus is regularly charged 6 times during 20ms (20ms is period of 50Hz supply), this result in dv/dt rise at the rectifier output with frequency 6-times AC supply frequency.
6pulses * 50Hz = 300Hz pulses in leakage current.

施耐德電機Taiwan

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings