Examples of MODICON M580 ePAC Networking Architectures
Issue
Examples of MODICON M580 ePAC Networking Architectures

Product Line
Unity

Environment
Windows 10


Resolution

The following examples are selected for presentation based on criteria which attempts to address
some of the most likely needs for Ethernet Connectivity of MODICON M580 ePAC Systems into an
End User's Ethernet Networking Infrastructure.
There are many needs that should be evaluated before committing to connectivity methods, these
include:

1. Standardized and Minimized Part Numbers vs. Lowest Cost
2. System likelihood to expand or require additional communication requirements
3. Remote Management (Network Transparency) of an entire M580 ePAC system (HART, Drives, etc.)
4. SCADA (Control) Network connection Speed (100 MB vs. 1 GB) and Throughput Management
5. Redundant SCADA (Control) Network connectivity
6. Owner of the Infrastructure (IT vs. Controls Engineering) and the IT Proficiency Level of the Owner
It is highly recommended to consult with your Schneider Electric Technical Sales Consultant to validate Quantum and M580 Ethernet IO Network Architectures.
This Legend is applicable to all of the examples that follow:
Click for a Larger Image


This first example is strictly applicable to systems that will only include 'BMX' Part Numbers
(excluding the CPU).  If System Expansion at the Control Network Level is possible, including,
adding EIO Drops or 'BME' or 'PME' Modules, then this example cannot be used.  The minimum
number of IP Addresses required on the Control Network by the M580 ePACs is 7 (eDIO Device count=0).
This example will potentially include 318 IP Addresses on the Control Network for the M580 ePACs
and their eDIO Devices.

Click for a Larger Image
This second example removes the limitation of only including 'BMX' Part Numbers, but has Device
Access and System Management limitations.  The minimum number of IP Addresses required on the
Control Network by the M580 ePACs is 6 (eDIO Device count=0, eDIO at BMECRA excluded).
This example will potentially include 304 IP Addresses on the Control Network for the M580 ePACs
and their eDIO Devices.


Click for a Larger Image



The third example demonstrates an alternative method of Securing and providing Total System
Management for an M580 System.  The minimum number of IP Addresses required on the Control
Network by the M580 ePACs (as shown) is 11 (eDIO Device count=0, eDIO at BMECRA excluded).
The addition of HART Analog modules to the far right system will increase this minimum count by
1 IP Address per HART Module.
This example will potentially include 374 IP Addresses on the Control
Network for the M580 ePACs and their eDIO Devices.
Click for a Larger Image

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings