我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Unable to establish communication in PME with Eton93PM even when the webpage is accessible and the IP address pings OK
Issue
Unable to establish communication in PME with Eton93PM even when the webpage is accessible and the IP address pings OK.



Product Line
Power Monitorirng Expert third-party device type

Environment
PME communication with third-party devices

Cause
No communication to Eaton93PM in Power Monitoring Expert.

Resolution
  1. Log in to the Eaton93PM, select the Network option from the left side and select Reboot Now as shown on the screen shot below just below the "HTTP get test"
  2. It will take about 2 minutes for the reboot to compete, PME will see the device as soon as the reboot completes

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings