Why do I see an impact on the cycle time when I update my M580 CPU to SV2.50 ?
Enhancements have been made in SV2.50 to enhance the reliability of the access to the internal memory (activation of the ECC : Error Correcting Code activation).

In most cases, very limited impact has been measured on the cycle time of typical applications.
The biggest impact is on some redundant M580 CPU systems (hot standby) where the cycle time may increase if your application has a very small code to execute but a big set of data to manage. (ECC feature only impacts hot standby memory transfer activity, and has very little impact on user code execution performance).

Possible workarounds are to :
- reduce the amount of exchanged data from primary to standby CPU
- disable the ECC feature using system word %SW150.
->To disable ECC: write the value 16#DECC to %SW150 (and power cycle the CPU (note: this value has to be written again after a cold start using the reset button).
->To re-enable ECC after a disable: write any value different of 16#DECC  to %SW150, perform a power cycle or push reset button.

- The status of ECC is given in %S109 : 0 = ECC activated, 1 = ECC deactivated.

Note: %SW150 is transferred from primary to stand-by PAC but the Standby PAC must also be power cycled to disable ECC. Verify that %S109 is set the same in both the Primary and Standby.

Basics :
- ECC (Error Correcting Code) corrects modern memories random access errors, but can slow down the memory access time.
- ECC feature only impacts  hot standby memory transfer activity, and has very little  impact on user code execution performance.
- ECC disable feature (%SW150, %S109) is only supported in M580 Hot Standby systems.
- Memory management optimizations have been deployed to compensate memory access time degradation.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings