What causes an SoF [Overspeed Fault] on an ATV630, ATV930 or ATV340?
Issue:
What causes an SoF [Overspeed Fault] on an ATV630, ATV930 or ATV340?

Product Line:
ATV630, ATV660, ATV680
ATV930, ATV960, ATV980
ATV340

Environment:
All serial numbers

Cause:
SOF during acceleration.

Resolution:
This fault can be caused by incorrect motor nameplate information in the drive, incorrect motor control settings for the application, or problems with the encoder feedback signal (ATV930/ATV340).
To resolve, go to the Main menu and Simply Start menu to ensure the motor nameplate information is correctly entered:
Nominal Motor power (nPr)
Nom Motor Voltage (unS)
Nom Motor Current (nCr)
Nominal motor Freq (FrS)
Nominal motor Speed (nSP)
If problem remains, goto Complete Settings (menu 5) / Motor parameters / Motor data and change Motor Param Choice to Mot Cosinus.  Then enter the Power Factor of the Motor in parameter Motor 1 Cosinus Phi.
Also under Motor Parameters try changing to a different Motor Control Type.  Selection may depend on the drive and the application, but common settings are U/V VC Standard or U/F VC 5pts.

If an Encoder is used, review the encoder wiring, programming and mechanical connection to the motor.􀁺 Instability or driving load too high.
􀁺 If a downstream contactor is used, the contacts between the motor and the drive have not been closed before applying a Run command
Remedy
􀁺 Verify the motor parameter settings.
􀁺 Verify the size of the motor/drive/load.
􀁺 Verify and close the contacts between the motor and the drive before applying a Run command.
Clearing the Error Code
This detected error requires a power reset.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings