Issue:
The following error is displayed when trying to open the Database Manager: cannot open the Database Manager. To open the Database Manager a user must be a member of the SQL sysadmin server role.

Description of sysadmin server role error from SQL

Product Line:
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023

Environment:
Database Manager
SQL Server Management Studio (SSMS)

Cause:
The 'sysadmin' role is not applied to the user account in SQL.

Resolution:
In order to use the Database Manager in Power Monitoring Expert 8.1 and newer, the user must log into Windows using an account that has been granted 'sysadmin' role in SQL Server Management Studio.

*Warning: Irreparable Database Damage can occur.  This procedure should only be performed by users familiar with SQL Server Management Studio.  Databases should be backed up prior to performing this procedure.*
Note: In some cases, a domain account may appear to have the 'sysadmin' role checked in SQL but are still unable to log in due to domain policy restrictions. To check and see if the user account does indeed have 'sysadmin' rights, the following query can be run in SQL Server Management Studio.

SELECT IS_SRVROLEMEMBER ('sysadmin',' <domain-user')

Checking server role and where to select

If the value returned is zero '0' the user does not have sysadmin rights.

Note: More information on how to determine if a SQL Server login is a member of a specified server role can be found in FA346467 .

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings