我们今天能为您提供什么帮助?
Which version of Vijeo Designer supports the HMIDT752 and HMIDT952?
Issue:
What version of Vijeo Designer supports the HMIDT752 and HMIDT952 screens for the Harmony (formerly known as Magelis) HMIGTU series?
Product Line:
Vijeo Designer, Harmony (formerly known as Magelis) HMIGTU
Resolution:
The HMIG5U2 is the current HMI CPU/Motherboard rear module in Vijeo Designer v6.2 that supports the HMIDT752 (15" Wide) and HMIDT952 (19" Wide) Touchscreens (as of August 2019).
Vijeo Designer v6.2 Service Pack 9 provides the HMIG3U the ability to use these touchscreens.
See the Table below for HMIGTU series support for these screens for each Vijeo Designer v6.2 Service Pack:
| Model | Service Pack 6 or older | Service Pack 7 | Service Pack 8 | Service Pack 9 |
| HMIG2U | N/A | N/A | X | X |
| HMIG3U | X | X | X | O |
| HMIG5U | X | X | X | X |
| HMIG5U2 | X | O | O | O |
Legend:
N/A - HMIG2U not introduced yet in this Service Pack
X - does not support the HMIDT752 or HMIDT952
O - supports the HMIDT752 or HMIDT952
Note:
In EcoStruxure Operator Terminal HMI configuration software (versions: Vijeo XD v3.0 or EcoStruxure Operator Terminal Expert v3.1+), both the HMIG3U and HMIG5U2 can use the HMIDT752 and HMIDT952 displays.
This is a different configuration software than Vijeo Designer.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
發佈於: 施耐德電機Taiwan