我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Power Monitoring Expert - the Energy Period over Period report will miscalculated energy total if an outage occurred and ION meter used 'Insert Outage Records' feature to zero fill missing readings
Issue
If an Energy Period over Period report is run against data that has had zeros inserted for missing data points, the report will miscalculate the energy totals. See attached screen capture for an example of what you might see.

Product Line
Power Monitoring Expert 7.2.x/8.x
Struxureware Power Monitoring 7.0.1

Environment
Web Applications 'Reports'

Cause
Some ION meters have a setup register option in the Data Recorders that will zero-fill missing records if a power outage has occurred. From the ION Reference:

The Data Recorder module Insert Outage Records option lets you determine how the meter handles logged information after a power outage. Upon the restoration of power, the meter can determine how many logged intervals have been missed due to the power outage, and based upon this programming option, can either leave the logs missing (this is the default functionality) or can fill in the missing logs with zero values.

The report handles the outage incorrectly. kWh is an accumulated value, therefore the report calculates energy values per interval by taking the difference between the one interval reading and the previous interval. But after an outage and with zero-fill enabled the previous kWh reading will be zero. So the first value will be the entire kWh total reading on the meter which is then calculated into the hourly or daily total, depending on the aggregation period chosen.

Resolution

*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

The recommended resolution is to manually correct the zero-value data points with approximations based on the consumption pattern. Power Monitoring Expert 9.0 will include a Manual Data Editor tool that will allow this to be done relatively easily.

施耐德電機Taiwan

附件
report_outage.png [223.7 KB]
探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings