IEC61850 configuration Tool returns the message 'Detected Error in Application'.
Issue
'IEC61850 Configuration Tool' returns 'Detected Error in Application' message.

Product Line
BMENOP0300

Environment
Unity, Windows 10


Resolution
Opening the IEC61850 Configuration Tool returns the message 'Detected Error in Application'.
fggg



The reasons that this occurs could be due to the 'MongoDB' services are not running or they were not properly installed.


To verify that the service are running:
  • Open the 'Computer Management' console.
  • Examine the status of the three (3) Mongo DB services:
  1. MongoDB for SchneiderTools.
  2. MongoDB Infos for SchneiderTools.
  3. MongoDB Transactions for SchneiderTools.
gsgg


If the services are not running:
  • Right click on the service name.
  • Select 'Start '.
  • Retest.



If the services are running:
  • Check that it is not being blocked by either
  1. The firewall,
  2. Antivirus software,
  3. Antispyware software
  4. PC group policy
  • Retest



If the issue still occurs, use the following steps to resolve the issue.
  • Uninstall 'MongoDB 3.2.8 for SchneiderTools'
  1. Open the windows search bar.
  2. Copy the command 'msiexec.exe /x {672788DA-D1E4-41AA-B14D-F0D2044C1180}' and paste it to the Windows Run command text box.
  3. Click on OK.
  4. Click on 'Yes' in the 'Windows Installer' window that appears.
sgs
gsg


  • Reinstall 'MongoDB 3.2.8 for SchneiderTools' using the attached software named 'MongoDB 3.2.8 for SchneiderTools_1.0.9.0_RS_x64.msi.7z.
  • Reinstall the IEC61850 Configuration Tool.
  • Retest.



施耐德電機Taiwan

附件
MongoDB 3.2.8 for SchneiderTools_1.0.9.0_RS_x64.msi.7z [28.29 MB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings