我们今天能为您提供什么帮助?
Video: What does the small C mean in the upper right corner of the LTMCU display for TeSys T controller?
Issue:
Troubleshooting C Status on LTMCU Display for TeSys T Controller
Product Line:
TeSys T, LTMCU, LTMR
Environment:
All
Resolution:
When you are in system config mode, you will see a small "c" in upper right corner of LTMCU. This would mean that the unit can be programmed. This also means that the unit cannot be commanded to run unless the system is out of configuration mode.
To adjust this status mode from the keypad.
Troubleshooting C Status on LTMCU Display for TeSys T Controller
Product Line:
TeSys T, LTMCU, LTMR
Environment:
All
Resolution:
When you are in system config mode, you will see a small "c" in upper right corner of LTMCU. This would mean that the unit can be programmed. This also means that the unit cannot be commanded to run unless the system is out of configuration mode.
To adjust this status mode from the keypad.
- Arrow down to services and enter.
- Arrow down to config and enter.
- Press enter on end config.
- Arrow down to yes and enter.
- This will now hide the C on top right corner which confirms that you are no longer in config mode.
發佈於: 施耐德電機Taiwan