How to setup an Alarm Variable in EcoStruxure Operator Terminal Expert (formerly known as Vijeo XD)?

Issue:
Cannot find where in EcoStruxure Operator Terminal Expert (formerly known as Vijeo XD) to create an Alarm Variable.

Product Line:
EcoStruxure Operator Terminal Expert, Vijeo XD 3.0 or higher.

Resolution:




In order to setup an Alarm Variable in Vijeo XD, there are a few steps you need to make.

1) First create an Alarm Group by first selecting "Alarms / Events" and then press the + Alarm Group button
Selection menu
2) Create a variable to use as the Alarm Variable
3) Expand the Alarm Group and choose the type of alarm you would like to create (BOOL / LEVEL)
4) Press the +Alarm Button to add the variable that you created. (See below)
Menu

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.