Video: How do you change a Momentum Processor in Unity Pro?
Issue:
Changing Momentum Processor Type in Unity Pro
Product line:
Unity Pro with the Unity Momentum Processor
Environment:
Unity Pro
Resolution:
When working on a Momentum project in Unity Pro, you will need to follow the below steps on how to change the processor type.
1. Open Momentum Project
2. Double click on configuration to open
3. The processor will show current processor and firmware
4. On the pull down from the bus select the new processor and matching firmware version or higher
5. Build and save project and verify no errors
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.