Can I control the number of automatic restart attempts on my LTMR after a voltage dip condition has been detected?
Issue:
Need to limit the number of automatic restart attempts after a voltage dip condition occurs.

Product line:
LTMR Tesys T

Environment:
All models with LTM-E expansion module attached.

Cause:
Information is unclear in the current literature.

Resolution:
It is not possible to limit the number of restart attempts in the LTMR to a specific number of attempts.  The function can be disabled, set to "load shedding" mode, or set to automatic restart.  The function requires an LTM-E expansion module, it is not present in the LTMR without the expansion module attached.

There are three registers in the LTMR that track the number of restart attempts, depending on what type of restart occurred:

Auto Restart Immediate count: When a voltage dip occurs but the voltage returns to normal quickly (within the time set by the parameter " Auto restart immediate timeout" the LTMR will perform an immediate restart and increment the "Auto restart immediate count" by one.

Auto Restart Delayed count:  When a voltage dip occurs and the voltage remains low for an extended time (longer than the "Auto Restart Immediate Timeout" parameter) the LTMR will wait to attempt to restart the motor.  The amount of time the LTMR waits before attempting restart is set via the "Auto restart delayed timeout" parameter.  Once a delayed restart occurs, the LTMR increments the "Auto Restart Delayed Count" by one.

Auto Restart Manual Count:  If a voltage dip occurs and the voltage remains low for a time greater than "Voltage Dip Restart timeout" then an auto restart will not occur.  It will be necessary to cycle the run command to the LTMR in order to restart.   The LTMR records the number of times this occurs under the parameter "Auto Restart Manual Count".

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings