我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Power Monitoring Expert 8.x/9.0 - Some of the ION services will not start - 'Error 1053 - The service did not respond to the start or control request in a timely fashion'

Issue
In some environments, some ION services will fail to start after rebooting or restarting manually. The affected services by software version are:


Product Line
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0

Environment
At this time, it is not entirely clear why this only happens in some systems. It seems to correlate to some Windows Updates.

Power Monitoring Expert 9.0

  • ION Application Modules Core Services Host
  • ION Cloud Agent Service
  • ION Managed Circuit Service
  • ION Diagnostic and Usage Service
  • ION Log Subsystem Router Service
  • ION Software Data Processing Service
  • ION Software Modbus Gateway Service

Power Monitoring Expert 8.x

  • Application Modules CoreServicesHost
  • ION Diagnostic and Usage Service
  • ION Managed Circuit Service
  • ION Software Alarm Service
  • ION Software Modbus Gateway Service

You will see a popup error that states:
'Windows could not start the ION <service name> service on the Local Computer.
Error 1053: The service did not respond to the start or control request in a timely fashion


Cause
When signed .Net service executables start, an attempt is made to verify the digital signature. If this attempt takes longer than 30 seconds, the Windows Service Control Manager (SCM) does not allow the service to start, and you will see the error described above. It was recommended by Microsoft that this check be disabled prior to .Net Framework 4 and later via a setting in the service's config file, which is what was done in the older ION services. Microsoft stated that this was unnecessary when using the .Net framework 4.0 and later, so newer ION services did not include this element in the config files.

See this link for more information:
https://docs.microsoft.com/en-us/dotnet/framework/configure-apps/file-schema/runtime/generatepublisherevidence-element

In spite of what is said in the link above, it now seems that in some environments this config element is still necessary.

Resolution

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

This problem can be easily resolved by adding the element below to the affected ION service config file. Updated files are attached. There is a package for PME 8.2, and also for PME 9.0.

<configuration>
<runtime>
<generatePublisherEvidence enabled="false"/>
</runtime>
</configuration>


Note that the ION Diagnostic and Usage Service and ION Software Modbus Gateway Service do not have .config files, so they need to be added.
The required files are attached. There is a package for PME 8.2, and also for PME 9.0.

Deployment Instructions
Be sure to stop all ION services before deploying!
Extract the zip file corresponding to your PME version and copy these files and their folders into the Power Monitoring Expert directory, replacing the existing files.


Note: This issue was fixed in PME 2020.

施耐德電機Taiwan

附件
PME8.x.zip [7.16 KB]
PME9.zip [9.42 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings