我们今天能为您提供什么帮助?
BMENOC firmware upgrade procedure
Issue:
BMENOC firmware upgrade procedure
Product Line:
BMENOC firmware
Resolution:
1/ Use the Unity Loader utility.
2/ Connect the PC that is running the Unity Loader to the Ethernet communications module.
3/ Launch the Unity Loader.
4/ Click the <Firmware> tab.
5/ In the PC list box, select the .ldx firmware file.
6/ When connected with Ethernet, check that the MAC address indicated in the PLC box
corresponds to the MAC address marked on the connected Ethernet device.
7/ Check that the transfer sign is green allowing transfer from the PC to the Ethernet module.
8/ Click on <Transfer>.
9/ Click on <Close> when transfer is complete.
NOTE: Make sure that the firmware update security is set to allow firmware updates.
-----------
The Unity Pro DTM provides security services to the BMENOC0301/11 Ethernet communication module.
Enable and disable these services on the Security tab in the Unity Pro DTM.
a/ Open the Unity Pro DTM Browser in the Unity Pro M580 project.
b/ In the DTM Browser, double click on the BMENOC0301/11 module.
c/ Select <Security>
d/ Enable or disable (default) these items.
Firmware upgrade
Device configuration management using the FDR service
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
發佈於: 施耐德電機Taiwan