我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Database Manager Not Responding After Running a Trim or Archive Job

Issue:
When running an archive or trim task in Database Manager, the manager will return a "Not Responding" state (see picture below).

Database Archive

Product Line:
PME 7.2
PME 8.x
PME 9.x
PME 2021
PME 2022
PME 2023
PME 2024

Environment:
Database Manager

Cause:
This issue is caused when an archive or trim of a large portion of the database is selected. This can arise when a large time frame is selected as the start and stop date.

Resolution:
Although an error is displayed, do not exit the manager. The job is still running in the background. You can check that the manager is still running by going to Drive:\Program Files X86\Power Monitoring Expert\Database and looking at the ION_Data.mdf file. You will see this file growing as the manager runs.


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings