In EcoStruxure Machine Expert / SoMachine, is it possible to create a Structure Variable consisting of mixed Persistent and Non-Persistent Variable leaf elements?
Issue
In EcoStruxure Machine Expert / SoMachine, is it possible to create a Structure Variable consisting of mixed Persistent and Non-Persistent Variable leaf elements?
For example, we wish to have MyINT and MyWord Non-Persistent and MyBOOL as Persistent below:

DUT Type Definition
TYPE MyStructType :
STRUCT
MyINT : INT;
MyWORD : WORD;
MyBOOL : BOOL;
END_STRUCT
END_TYPE
Structure Variable Definition in Global Variable List (GVL):
VAR_GLOBAL
ThisStruct : MyStructType;
END_VAR
Product Line
SoMachine
EcoStruxure Machine Expert
Environment
PLC Configuration Software
Resolution
No. It is not possible to create a Structure Variable that has leaf-element Variables that consist of mixed Persistent and Non-Persistent Variables.
Fully Persistent Structure Variables must be defined in the PersistentVars object, while Non-Persistent Structures must be defined in either a POU's Variable Definition box or the Global Variable List (GVL) separately.
Example:
The original Structure from the above Example can be split into two Structures defined in the GVL and PersistentVars objects.
DUT Type Definitions
1) Meant for Non-Persistent:
TYPE MyStructType :
STRUCT
MyINT : INT;
MyWORD : WORD;
END_STRUCT
END_TYPE

2) Meant for Persistent:
TYPE MyPersistentStructType :
STRUCT
MyBool : BOOL;
END_STRUCT
END_TYPE
Structure Variable Definition in Global Variable List (GVL):
VAR_GLOBAL
NonPersistentStruct : MyStructType;
END_VAR
Structure Variable Definition in PersistentVars:
VAR_GLOBAL PERSISTENT RETAIN
PersistentStruct :  MyPersistentStructType
END_VAR

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings