我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What can cause an Internal Error 12 (InFC) on the ATV630 and ATV930 Process Drives?
Issue:
ATV630/ATV930 InFC or internal error 12

Product Line:
ATV630 and ATV930

Environment:
All

Cause:
Internal current supply error
- Defect of the current transformer
- Defect on the power supply on the inverter / AFE power board

Resolution:
This error could occur on S6, ATV•30F, ATV•50F, ATV•60 and ATV•80.
The InFC error is raised when the current sensor supply monitoring has detected a low level on the current sensor supply.

- Check with SoMove service section, on which brick the fault occurs
Power OFF the drive and disconnect the current transformer of the identified brick,
Power ON the device and check if the fault raised again, if the fault is not present the current sensor is damaged - > change the brick.
If the fault raised again, change the inverter board or AFE brick power board of the identified Brick

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings