我们今天能为您提供什么帮助?

What Lonworks communication options are available on the ATV630 and ATV930 Process drives?

Issue:
Is Lonworks available on the ATV630 and ATV930 drives?

Product Line:
ATV630 and ATV930 drives.

Environment:
All

Cause:
Available options

Resolution:
The ATV630 and ATV930 drives do not currently have an option for Lonworks.  If you need to use Lonworks on the ATV630 and ATV930 drives you need to add a third party gateway.

施耐德電機Taiwan

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。