EcoStruxure Control Expert 14 returns message Integrity Check - C:\Program Files (x86)\Common Files\Schneider Electric Shared\SRCSDK\Srcsdk.dll
Issue
If I open 'EcoStruxure Control Expert' after installing the software, I get a message indicating 'Integrity Check - 'C:\Program Files (x86)\Common Files\Schneider Electric Shared\SRCSDK\Srcsdk.dll'
If I click on OK to close the message window, 'Control Expert' starts up.

Product line
EcoStruxure Control Expert 14.

Environment
Windows 8, Windows 10

Resolution
The following steps can be used to resolve the issue:
  1. Navigate to the path described in the 'Integrity check' error window ('C:\Program Files (x86)\Common Files\Schneider Electric Shared\SRCSDK).
  2. Locate the file named 'IntegrityCheckSRCSDK.bin'
  3. Delete the file.
  4. If there are multiple files starting with the name IntegrityCheck...bin, delete those as well.
  5. Insert the DVD for Unity and run 'setup.exe'.
  6. If you get an error regarding the installation of 'Microsoft Visual C++ 2012 Update 4 Redistributable...have failed) Do you want to continue with the installation,' click on 'Yes' to proceed.  The reason for the failure message  is due to the  software already being installed on the PC.
  7. Click on 'Next'.
  8. Select 'Repair to repair the installation.
  9. Launch the application after installation repair completes.

Schneider Electric Shared\SRCSDK\Srcsdk.dll | 施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings