我们今天能为您提供什么帮助?
Can I use a Vijeo Designer recipe object from the Webgate ?
Issue:
There are certain limitations while using Recipe objects in Web Gate.
Product Line:
XBTGT
HMIGTO
HMIGTU
IPC with VJD Runtime
Resolution:
The Data Sharing for the recipe control variable (_RecipeControlDefault) must be set to None.
Also the Internal Recipe variables associated to the ingredients must be set to none.
The external Recipe variables associated to the ingredients can be set to Read/Write.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
發佈於: 施耐德電機Taiwan