How is the ATV212 set for RUN/STOP on the terminals and speed reference from the keypad UP/DOWN arrows?

Article available in these languages:

Issue:
How do you change parameters on the ATV212  for RUN/STOP on the terminals and UP/DOWN arrows for the speed reference.

Product Line:
Altivar Machines, Altivar 212

Resolution:

Press Mode until you see AUF
Scroll to CNOD, enter 0 for terminals Start/Stop control.
Scroll to FNOD, enter 3 for keypad UP/DOWN arrow button speed control.