我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What are the cables needed for communication between a Magelis HMIGTO and Modicon M221 PLC?
Issue
What is are the cables needed for communication between a Magelis HMIGTO and Modicon M221 PLC?

Product Line
Magelis HMIGTO, Modicon M221 PLC

Environment
Serial Cable for communication

Resolution
For serial communication between the COM1 RJ45 of a Magelis HMIGTO and Modicon M221 PLC, you will need:

For RS-232C communication:
One XBTZ9720 cable
and two adapters: XBTZG939

For RS-485 communication:
One XBTZ9980 cable

For configuration from a PC using the USB mini-B ports on either the HMIGTO5310 or M221 PLC, you will need:
BMXXCAUSBH018 (USB-A to USB-mini-B cable)
The Magelis HMIGTO series can also be configured using Ethernet.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings