我们今天能为您提供什么帮助?
How to convert bits to an Integer in Vijeo Designer?
Issue:
Looking for a script method to convert bits to an Integer in Vijeo Designer?
Product Line:
Vijeo Designer (all versions)
Resolution:
To convert bits to be used an Integer variable in Vijeo Designer, please use a script as shown below:
boolean bitArray[] = new boolean[16];
int value = 0;
bitArray[0] = true;
bitArray[1] = true;
bitArray[2] = true;
bitArray[3] = true;
bitArray[4] = true;
bitArray[5] = true;
bitArray[6] = true;
bitArray[7] = true;
bitArray[8] = false;
bitArray[9] = false;
bitArray[10] = false;
bitArray[11] = false;
bitArray[12] = false;
bitArray[13] = false;
bitArray[14] = false;
bitArray[15] = false;
for (int i = 0; i < 16; i++)
{
if (bitArray[i])
{
value += 1 << i;
}
}
//TestINT is a Vijeo Designer INT variable that I created. This was just used to test the output.
TestINT.write(value);
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
發佈於: 施耐德電機Taiwan