{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

EBO SNVT types of third party devices doesnt match with SNVT types in TAC Vsta

EBO system processes data from third party LonWorks devices according definition by Device Template which is imported to a Building Operation Server (ES/AS-P).

In case SNVTs types visible in EBO don't match with SNVTs in TAC Vista database after conversion procedure was done, there must be discrepancy in XIF files which have been imported in advance.

Check up Network Variable index numbers for particular SNVTs which do not match after conversion against XIF files.

Make XIF file correction manually following LonMark org Technical Resource guide
http;//www.lonmark.org/technical_resources/resource_files/1500/snvt.pdf

施耐德電機Taiwan

探索更多
系列:
探索更多
系列: