Can I use TeSys island in a Ring Topology?
Issue:
Does TeSys Island support ring topology
Product Line:
Tesys Island
Environment:
Digital multifunctional load management solution
Resolution:
Yes, RSTP is enabled by default when storing a configuration from the DTM. Make sure to use the 2 fieldbus ports, as it is not enabled for the top Service port.