PME 9.0 - Cannot deactivate alarms in Management Console if logged in as a non-admin domain Windows users

Issue
Try to use Management Console's "Deactivate Alarms" feature, as a non-admin user, to deactivate one or more of those active alarms and the following error will appear:

"an unexpected condition was encountered while initializing the AlarmInactivator: Write to Primary data queue failed.."



Product Line

Power Monitoring Expert 9.0

Envorinment
Management Console -  "Deactivate Alarm" feature

Cause
PME's MQ setup uses the "Everyone" bucket for permissions and permissions set for the "Everyone" group DO NOT APPLY to domain users by default.

Resolution

Resolution 1:
Run Management Console "As Administrator" (i.e. the right-click menu in Windows).

Resolution 2:
1. Log in as administrator of the server
2. Open the Windows Start menu and search "Computer Management"
3. Open Computer Management then expand Services and Applications > Message Queues
4. Check permissions for all of the private queues by right-clicking on each of them and selecting Properties > Security
  • List of private queues to check:
    • cloudagent_control
    • cloudagent_data
    • logsubsystemprimaryrouter_control
    • logsubsystemprimaryrouter_data
    • logsubsystemsecondaryrouter_control
    • logsubsystemsecondaryrouter_data
  • Make sure each of the queues listed above have the following permissions:
    • "Everyone" group has access to allow:
      • Get Properties
      • Get Permissions
      • Send Message
    • "Administrators" group should have full access to the queue
    • "ANONYMOUS LOGON" Group should only have access to:
      • Send Message
5. If the issue persists (and using Windows domain account), add the domain group to the security tab and allow permissions to:
  • Get Properties
  • Get Permissions
  • Send Message
6. Restart "Message Queuing" service in Services

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings