How is the Linergy FC Selection Table for Special Cases from the Prisma P catalog used?

The following table indicates the values of maximum permissible current Inc of the Linergy FC for temperatures inside the switchboard.  These values are for conditions that are not like most installations, where the outside temperature is 40°C and 60°C inside the switchboard.
Linergy FC selection table for special cases
correction factor table for thermal magnetic NSX
NSX catalogue LVPED217032EN, 2019. Page E-14.

The maximum permissible current of the circuit breaker must be determined from the temperature derating table published in the product catalog (example above).
After the temperature correction factor of the circuit breakers is considered and the diversity factor applied, the result must be less than the Linergy FC maximum permissible current Inc.

diversity factor K
Note that K and RDF are equivalent terms in our case.

Examples:

Example 1: For a Linergy FC with up to 4 x NSX250 3p, installed in a switchboard with 40°C inside temperature, the Inc is 800A.
At 40°C, the correction factor determines the NSX250-TM250D setting to be: 1.00 x 250 = 250A.
The maximum permissible current (RDF = 0.8) for the 4 x NSX250-TM250D units is then:
4 x 250 x 0.8 = 800A
This is equal to the Inc.

Example 2: For a Linergy FC with up to 3 x NSX250 4p, installed in a switchboard with 60°C inside temperature, the Inc is 615A.
At 60°C, the correction factor determines the NSX250-TM250D setting to be: 0.90 x 250 = 225A.
The maximum permissible current (RDF = 0.9) for the 3 x NSX250-TM250D units is then:

3 x 225 x 0.9 = 607.5A

This value is less than Inc; 607.5A < 615A


Background:
RDF is based on IEC 61439-2 section 5.4
Rated Currents and diversity factor
Rated Currents and diversity factor (continued)
Extract from IEC specifications for LV assembly switchboards – In conformity with IEC 61439-1&2 standard; Specifiers Guide, pages 9-10.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings