我们今天能为您提供什么帮助?
Why doesn't my Vijeo Designer project build?
Issue:
Vijeo Designer application does not build and the feedback zone has several compile errors. The compile errors are indicating that a file cannot be written and access to a folder cannot be obtained.
Product Line:
Vijeo Designer (all versions)
Resolution:
When your Vijeo Designer application cannot build due to a compiler error stating a file cannot be written, check to see if you have any firewall applications running on your PC blocking Vijeo Designer. As an example, BitDefender blocks our Java Compiler "jikes.exe". You will need to ensure that this application is allowed to run in order to properly build your Vijeo Designer application.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
發佈於: 施耐德電機Taiwan