PME - Web Applications login page shows "Unregistered system"

Issue
After activating permanent licenses on a newly installed or recently upgraded system, the login page for the Web Applications shows "Unregistered system".

image of message

Product Line
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024


Environment
Web Applications

Cause
This message is a reminder to register the product with Schneider Electric to enhance service and help provide better support, similar to the "this product is not registered" pop-up when opening Management Console on older versions of PME. From the PME 2023 System Guide:

"Registration Information will be used by Schneider Electric to help provide support and to enhance the service we provide to you.

Schneider Electric will never sell nor share this information.

By registering you acknowledge that your registration information will be shared with Schneider Electric and you consent to receiving occasional communications about your product.

Product communication includes new features, service pack releases, and recommended cybersecurity updates."

Resolution

  1. Log in to the Web Applications
  2. Open the Settings tab
  3. Select Registration Information
  4. Review the Terms and Conditions, then check the box for "I have read and accept the Terms and Conditions"
  5. Fill in any applicable fields then click Save at the bottom of the page to complete the product registration


image of information to fill out

how the login page will look post registration

Notes:

  • It is not required to enter an email address to complete product registration
  • Information shown under "Login screen information" is a preview of what will be shown on the login page for the Web Applications
  • The City, Region/State, Contact Email, and Website fields specifically are not shown on the login page, so if the user would only like to clear the "Unregistered system" message and not display any other information, fill out at least one of these fields then click Save

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings