我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
PME9.0 - PME Diagnostics Tool cannot retrieve log from ION_SystemLog
Product Line
Power Monitoring Expert 9.0

Envorinment
Diagnostics Tool 9.0

Issue
In the Diagnostics result, an error "The conversion of a varchar data type to a datetime data type resulted in an out-of-range value" is inserted into ION_SystemLog part, and no logs are retrieved from database.


Cause
Depending on the Regional Settings, the tool cannot parse the data type. This will happen when the Format setting in Windows Region is set to English (Finland) for instance and it can happen for different region settings as well.
Please, do NOT change the system locale (in the Administrative page).

Resolution
Change the Format setting to English (US) to run the tool or use SQL to obtain the ION_SystemLog information.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings