I don’t have an internet connection and I would like to activate my EcoStruxure Control Expert license
Title
How to activate EcoStruxure Control Expert license

Issue
Activate EcoStruxure Control Expert without an internet connection

Product Line
EcoStruxure Control Expert

Environment
EcoStruxure Control Expert

Cause
Since no internet connection is present, the Schneider Electric License Manager cannot connect to the Schneider Electric Licensing Server

Resolution
Control Expert Activation by Phone Method (not available for Virtual Machine environment without internet connection)
  1. Ensure that you have aWeb User Management / Software Licensing Portal account. If you haven't created one, go to https://schneider-electric.com/licensing and follow the instructions.
  1. Open the Schneider Electric License Manager then click the Activate button.
License Manager 0
License Manager
  1. Click "Use another activation method"
License Manager 2
  1. Click "By phone" and read the Instruction box then click Next
License Manager 3
  1. If EcoStruxure Control Expert is installed, it should appear on the Product Selection screen. Click the correct product that you would like to activate then click Next
License Manager 4
  1. Enter your EcoStruxure Control Expert Activation ID then click Next
License Manager 5
  1. Enter your Web User Management / Software Licensing Web Portal account. If you haven't created one yet, go back to the instructions on Step 1
License Manager 6
  1. Call your Software Registration Center (SRC) and provide the information on the Complete Activation screen or send an email to your SRC with a screen shot of the Complete Activation screen
License Manager 7
  1. Enter the Response Code provided by the SRC Operator then click Next then Finish to complete the activation of your software.
License Manager 10

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings