我们今天能为您提供什么帮助?

Is there an alternative part for the HMIZGAUX?

Issue:
The lead time for the HMIZGAUX is quite substantial. Looking for an alternative part number for the same part.

Product Line:
Magelis HMI (XBTGT, HMIG3U, HMIG3X, HMIG5U, HMIG5U2)

Resolution:
If the lead time for the HMIZGAUX is too long, consider checking your suppliers for Phoenix Contact's equivalent part of: FK-MC 0.5-2.5 7 position. (1908114)

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings