我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Unable to open the Alarms tab after upgrading to PME 9.0

Issue:
The following message is displayed when trying to open the Alarms tab from the Web Applications
after upgrading to PME 9.0.
"Alarms is processing existing records for the first time use.
The Alarms application will be ready for use once the historical processing is complete"

error

PRODUCT LINE:
Power Monitoring Expert 9.0

ENVIRONMENT:
Web Applications in Power Monitoring Expert

CAUSE:
The Alarm tab is not opening and the Progress Report shows 0% complete even after the Refresh link
is pressed several times. The diagnostic system log shows this message below.
"Could not find Stored Procedure 'dbo.CleanCorruptincidentsAndAlarms"

RESOLUTION:
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with
SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*


*Warning: Take backups of any files prior to modifying them. Ensure the backups
are in a location that will not be overwritten (i.e. the Desktop).

Go to SQL Management Studio and run the attached SQL query to create the
'dbo.CleanCorruptincidentsAndAlarms Stored Procedure.
Once the query is run, verify the Stored Procedure is created under ION_Data\Programmability\Stored Procedures.


stored procedure

After verifying that the stored procedure has been created, restart all ION Services and check on the alarms processing progress in the Web Application Alarms tab

施耐德電機Taiwan

附件
Create_CleanCorruptIncidentsAndAlarms.sql [2.89 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings