PME Web Alarms show "Unable to update the result. The server either timed out or returned invalid result."

Issue
PME Web Applications Alarms tab does not show Alarms and a red error message appears stating: 'Unable to update the result. The server either timed out or returned invalid result. If this problem persists please contact the system administrator.'

Unable to update results
In the PME ApplicationModules log, the following errors are shown:

  • Failed to load the resx file 'EnumAndEvent' for the culture 'en', --- >
    System.IO.FileNotFoundException: Could not find file 'C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc\EnumAndEvent.en.resx'.
  • Failed to load the resx file 'IONNames' for the culture 'en', --- >
    System.IO.FileNotFoundException: Could not find file 'C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc\IONNames.en.resx'.

Product Line
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024


Environment
Web Applications

Cause
The language associated with EnumAndEvent.en.resx and IonNames.en.resx are not reading correctly.

Resolution

1. On the PME server, navigate to …\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc

2. Make a copy of the EnumAndEvent.en.resx and IONNames.en.resx files

Copy files

3. Rename the copies to EnumAndEvent.en-US.resx and IONNames.en-US.resx

Rename files

4. Open the Windows Start menu and search for "Command Prompt"

5. Right-click on Command Prompt > Run as Administrator

6. Type the following command then press Enter to run:

  • iisreset

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings