我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Why my PowerTag Sensors cannot communicate with SmartLink SIB / SID ?
If you have checked the basic commissioning steps (Smartlink powered on, pairing, communication periods, channel attribution) you can refer below.

This issue can occur for SmartLink SI D / SI B with old firmware revision when they are used in environment with high density wireless traffic (intensive RF environment). In this case, you need to replace your SmartLink SIB / SI D by a PowerTagLink A9XMWD20 or A9XMWD100.

Switch OFF / ON the wireless devices to commute the wireless device in "waiting for pairing" status and launch the wireless discovery on the gateway to pair them.
If you have not the possibility to switch OFF / ON you wireless devices (case of powertag associated to critical load) please contact your Schneider Electric technical support.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings