How to replace a serial meter with an Ethernet meter in Power SCADA Operation (PSO) 9.0.

Issue

A serial meter on an daisy chain was replaced with a new Ethernet meter. The Power SCADA Operation project must be updated so the new device communicates.

Product Line

Power SCADA Operations 8.2

Power Operation 2020 and 9.0

Power Operation 2021

Power Operation 2022

Power Operation 2023

Power Operation 2024

Environment

Device Manager

Device replacement

Resolution

  1. Open Power SCADA Studio.
  2. Go to Topology → I/O Devices and locate the row for the replaced device. Capture its parameters (I/O Server, Name, Protocol/Driver, etc.).
  3. Open I/O Device Manager (right‑side panel).
  4. In I/O Device Manager, select the active project → Manage a Single Device… → Remove one I/O device.
    • Complete the removal wizard and, when prompted, select Add / remove / update more equipment to continue.
  5. Choose Create one I/O device and select the correct device profile for the new Ethernet meter.
    • If the profile isn’t available, add it via Device Profile Editor, then export it to the project and return to I/O Device Manager. See FA404306 for instructions on how to add a device profile to a project.
    Reuse the exact same Equipment Name and I/O Device Name as the removed device to preserve existing tag/graphics bindings.
    • If the name differs (even syntax), a new tag set will be created and any graphics referencing the old tags would have to be edited.
  6. Select the same Primary Server (and Standby Server, if applicable) as the old device.
  7. Configure Modbus TCP communications (using the project’s Modbus driver—commonly PwrModbus when added via I/O Device Manager).
    • Enter the IP address of the meter and the Unit ID / Device Address required by the device:
      • Many TCP devices ignore Unit ID or expect 1.
      255 appears in some guides but is not universal.
      • For TCP→serial gateways, set the serial slave ID behind the gateway. Always follow the meter/gateway manual.
  8. Confirm the wizard’s Port Name; keep the new, unique name—do not reuse the old port name.
  9. Finish the I/O Device Manager workflow. Compile the project and restart the applicable I/O Server in Runtime so the device begins communicating.

Note: If the selected device profile adds driver parameters (timeouts, word‑order, etc.), review any driver/INI parameters in Setup Editor / citect.ini per the driver’s reference.

Recommendation:

If you are using an older version of

Power Operation, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo-psup@se.com

Support details

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings