我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Incorrect Diagram is opened in Vista despite pointing to the correct diagram file.
Issue
Third party driver opens incorrect diagram and there needs to be a way to determine where it's opening the incorrect diagram from

Product Line
PME8.x
PME9.0
PME2020

Environment
Vista

Resolution
When opening a diagram in Vista, the diagram should open from a pre-defined registry path where the device diagrams are associated to a Device type in the registry.  There may be times where a particular device diagram is not under the expected root path and so isolating the issue involved locating where it's opening from.  The following tool helps identify and filter the location of where the an incorrect diagram may be opening from
  1. First apply this index?page=content&id=FA212118.
  2. If an incorrect diagram is still being opened, then there is specific tool used for troubleshooting that can tell you exactly what registry entries any program is trying to access.
  3. Download Procmon64.exe (https://live.sysinternals.com/)
  4. Procmon is a tool that can tell you what registry entries any program is trying to access and the result
  5. Launch Procmon and stop capture (magnifying glass)
New Process Monitor
  1. Click on the filter button and add the following: Path contains \SOFTWARE\Wow6432Node\Schneider Electric\Power Monitoring Expert\8.2\DeviceInfo and then click apply
Note: The software name and version number after the \Power Monitoring Expert\ will vary depending on the version of software.
Monitor filter settings
  1. Start the Capture
Process monitor
  1. Open Vista and try to open the diagram page with open diagram from meter template of the device diagram in question
Diagram page
  1. Go back to Procmon and stop the capture
Process monitor
Process Name: Corresponds to the application opening up the diagram
Path: Corresponds to the path of the diagram which we filtered out in the previous steps
Result: The result of opening the diagram
  1. From here you would need to observe the path the incorrect device diagram is opening and that will allow you to pinpoint where it’s referencing the diagram.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings