我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Integrity check error is returned after running Control Expert following GPL Library install
Issue
Integrity check error is returned after running Control Expert following 'PSx GPL 2015 R2 for Unity Pro' Library install

Product Line
Control Expert

Environment
Windows 10.

Resolution
An integrity check error message gets returned after starting Control Expert 14.1 following the installation of the
'PSx GPL 2015 R2 for Unity Pro' library.

The issue can be resolved by performing the following steps:
  • Uninstall Control Expert 14.1
  • Reboot.
  • Delete the folder named ‘PSx GPL for Unity Pro’ from the folder named ‘C:\ProgramData\Schneider Electric\Control Expert 14.1'.  (Note: This folder does not get deleted by the uninstall, If a third party library is installed)
  • Install Control Expert 14.1
  • Install the hotfixes including HF1 (run Control Expert and close after each hot fix install.)
  • Install the ‘GPL_Communication’ family.
  • Run Control Expert 14.1
  • Close Control Expert14.1
  • Install the ‘GPL_Devices’ family.
  • Run Control Expert 14.1
  • Close Control Expert14.1
  • Install the ‘GPL_Diagnostics’ family.
  • Run Control Expert 14.1
  • Close Control Expert 14.1
  • Install the ‘GPL_Process’ family.
  • Run Control Expert 14.1
Note:

When you uninstall Control Expert, it should delete 'Control Expert 14.1 folder from both 'C:\ProgramData\Schneider Electric'  and
C:\Program Files (x86)\Schneider Electric.  If it doesn't, then you will need to manually delete them.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings