我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Connecting to an M340 with USB returns 'An incorrect structure size was detected' error message.
Issue
Connecting to an M340 with USB returns 'An incorrect structure size was detected' error message.

Product Line
M340

Environment
Unity, Control Expert.

Resolution
Attempts to connect to the M340 using USB returns the error message 'An incorrect structure size was detected'.

This issue occurs when the 'Schneider PLCUSB Driver' is used to connect to an M340 with either Control Expert or Unity running on a Windows 10 (Build 1803) PC.

This is due to an unexpected change by Microsoft on the Windows Remote Access Services (RAS) API. It is corrected in the KB4103721 update from Microsoft released May 8, 2018.

To resolve the issue, install Mincrosoft Update KB4103721.which can be downloaded from:

https://www.catalog.update.microsoft.com/Search.aspx?q=KB4103721

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings