What is the time limit for BMX Analog inputs to withstand their specified isolation voltage values?
Issue
The isolation voltage specifications for BMX Analog inputs do not specify a time limit. What is the time limit for the isolation voltage specifications?
Isolation voltage example for a BMXAMI0810
Product Line
x80 Analog inputs
Resolution
There is no isolation voltage time limit. The module can withstand the maximum isolation voltage indefinitely without any damage.