How can I setup Java to access webpage of STB under Win10/7 OS ?

1.Issue

How can I setup Java to access webpage of STB under Win10/7 OS ?

2.Environment

Windows 10 ,Windows 7,  32bit or 64bit

3.Resolution

User could install jre-8u202-windows-i586.exe for Win7 and Win10 OS and remove other Java versions from control panel.

The installation file could be downloaded in
https://www.oracle.com/java/technologies/javase/javase8-archive-downloads.html
After installation of Java ,  the security level should be selelcted to High and the webpage address of STB should be added to execption site


JAVA setting

The webpage of STB should be opened by Internet Explorer and user should choose later option when Java update needed window pops up .

java diag

User needs to accept the security warning and click run button when this window appears .

Web security
The default HTTP feature of STB NIM has been disabled due to cybersecurity enhancement if the firmware version of manufactured module is listed  as following
STBNIP2311 SV>=5.0
STBNIC2212 SV>=4.0
STBNIP2212 SV>=4.0

User could install latest Advantys configuration tool ,enable the HTTP feature in module options ,then online the STB to download the configuration.
The download link for Advantys configuration tool is  ​​​​​https://www.se.com/ww/en/search/STBSPU1000_Software

http feature selection

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings