Control Expert returns 'Failed to find a valid license' after activation of a floating license..

Examination of the file named 'License Manager_reg' shows:

ERROR: Failed to load TS, try to repair TS segment
ERROR: Failed to create transaction handle: Error: 51401
Found 1 fulfillments in Trusted Storage


The issue occurred due to the trusted storage in the PC to have been broken and the self-healing mechanism of the LMBrick is not able to fix it.

The solution would be to delete the trusted storage files and activate then all licenses again.

Use the following steps to delete the trusted license (Note: All license data on a PC are stored in the trusted storage files. By removing those files all licenses on a PC will get lost.)

  • Open the Schneider Electric License Manager (LM).
  • Record the Activation ID and part number..
  • Select the and click on the Floating license checkbox.
  • Click on 'Return' to return the license.

cv

  • Open the folder named 'C:\ProgramData\FLEXnet'.
  • Delete the files named:
    • schneide_0098df00_tsf.data
    • schneide_8098df00_tsf.data
    • schneide_0098df00_event.log
    • schneide_8098df00_event.log
    • schneide_0098df00_tsf.data_backup.001
    • schneide_8098df00_tsf.data_backup.001.

sfvv

  • Reactivate the Floating license.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings