我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Can the Masterpact MTZ open close coils be monitored for health?

Issue: Trip Coil Supervision (ANSI 74)
Product Line: Circuit Breakers
Environment: Masterpact MTZ

Resolution:
The Micrologic X control unit continuously monitors the electrical continuity of the circuit breaker open/close coils. It generates an alarm if a problem is detected.  Use the diagnostic and communication coils.
diagnostic coils
Shunt Close (XF), Shunt Trip (MX), and Undervoltage Release (MN) with Diagnostic and Communicating Coils bring added functionality with diagnostic and communication capabilities:
• Identify the type of the coil, MX diag&com, XF diag&com or MN diag.
Detect if the coil is functioning properly by comparing the device order and the
opening/closing status of the circuit breaker.
• Check for wire breakage in the coil periodically (every 30 seconds).

• Identify if the order comes from the BPFE option.
• Identify if the order is a permanent order.
• Count the operating cycles of the coils.
Results can be read through all the different ways of retrieving information from the Micrologic X control unit, including the embedded HMI, wireless communication, and EcoStruxure Power Commission (EPC) software through a USB connection. If the coils are connected to the communication system, results can also be accessed through the communication system.


施耐德電機Taiwan

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings