What is an SOC fault on the ATV320?

Issue:

SOC fault on ATV320 drive.

Product Line:

ATV320

Product Line:

All

Cause:

Clarification of product characteristics.

Resolution:

SOC indicates "Output Cut" status so its not a fault.

This is related to the Output Phase Loss function.

Output phase loss is used to detect when one or more phases of the motor are pulling no current (open connection to motor).

It also can detect an imbalance in current draw between phases and trigger a fault if the imbalance is too great.

By default the Output phase loss parameter is set to YES, which means the drive will fault on an Output Phase Loss fault if there is a phase loss or significant current imbalance on the motor leads.

The Output phase loss parameter can be changed to No , or OAC Output Cut.

When it is set to OAC, SOC is displayed when the function is triggered (no motor is detected when commanded to run or motor is disconnected while running).

In this mode, once an output phase loss is detected, the drive will stop the motor and display SOC on the screen but will not trigger a fault status.

When set to No the drive will not monitor for a phase loss or phase imbalance in the motor connections. External phase loss protection should be provided.

This is the standard setting on enclosed drives that have a full voltage bypass, because the overload relay provided with bypass provides that protection.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings