我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to change the SiteManager Token Domain for Windows target?
For some reason, if you need to change the token domain of one SiteManager on Windows Target, you cannot just update the Domain Token name and reconnect. In this case, the SiteManager will still try to connect to the previous Domain Token
The goal of this FAQ is to explain how to do it

This article is applicable for the part SiteManager of EcoStruxure Secure Connect Advisor on Windows target

To update the Domain Token, need to reset the SiteManager information
To do it, need to execute the batch file ReConfig SiteManager Embedded located in SiteManager folder
Capture.PNG

After executing the batch file, all information of SiteManager will be reset and you will be able to change the Domain token

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings