Masterpact MTZ Micrologic X Maintenance Alarms and Service LED

Article available in these languages: 西班牙文

Issue: How to complete the Basic, Standard and Manufacturer Maintenance alarm and declare maintenance done with EPC
Product Line: Circuit Breakers
Environment: Masterpact MTZ Micrologic X control unit

Resolution:
Micrologic control unit

Alarm Frequency:
  • Basic - around one year- basic operations
  • Standard - around two years - basic operations + dedicated set of standard operations
  • Manufacturer - around 5 years - specific manufacturer operations
What maintenance needs to be done and what is the time required for experienced, trained, and qualified personnel
to perform this maintenance program?
  • The list of maintenance items and procedure reference number can be found in the Masterpact MTZ maintenance guide document DOCA0099EN
  • Basic and Standard end user "how to" maintenance procedures are located in document DOCA0103EN
  • Basic - 15 minutes for a fixed device, 20 minutes for a drawout device. Standard - 45 minutes for a fixed device, 1 hour for a drawout device.  Manufacturer - From 1.5 hours to 2 hours depending on the frame size, for a fixed device. From 2 hours to 3 hours depending on the frame size, for a drawout device.
How to declare the completed maintenance to complete the alarm and make the alarm and Service LED go out.
  • Use EcoStruxure Power Commission software (EPC)
  • Once connected, click the Device Check Up box, click the Maintenance tab, go to Last Maintenance Details box and click View History.
  • Edit the Date, Company in charge, maintenance operator name.
  • Enter password and save data
  • The Service LED will now go out.
EPC screen shots:
EPC image

EPC image
EPC image

EPC image

How to enable/disable maintenance alarms:
  • Disabling maintenance alarms is not recommended unless you have a robust maintenance schedule that matches the alarm frequency.
  • Use EPC software
  • Once connected click the configure box, click the alarms tab, then click Maintenance on the left
  • Scroll down to the basic, standard or manufacturer alarm to enable/disable
EPC image

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings