我们今天能为您提供什么帮助?
Masterpact MTZ Micrologic X Maintenance Alarms and Service LED
Issue: How to complete the Basic, Standard and Manufacturer Maintenance alarm and declare maintenance done with EPC
Product Line: Circuit Breakers
Environment: Masterpact MTZ Micrologic X control unit
Resolution:

Alarm Frequency:
to perform this maintenance program?




How to enable/disable maintenance alarms:
Product Line: Circuit Breakers
Environment: Masterpact MTZ Micrologic X control unit
Resolution:
Alarm Frequency:
- Basic - around one year- basic operations
- Standard - around two years - basic operations + dedicated set of standard operations
- Manufacturer - around 5 years - specific manufacturer operations
to perform this maintenance program?
- The list of maintenance items and procedure reference number can be found in the Masterpact MTZ maintenance guide document DOCA0099EN
- Basic and Standard end user "how to" maintenance procedures are located in document DOCA0103EN
- Basic - 15 minutes for a fixed device, 20 minutes for a drawout device. Standard - 45 minutes for a fixed device, 1 hour for a drawout device. Manufacturer - From 1.5 hours to 2 hours depending on the frame size, for a fixed device. From 2 hours to 3 hours depending on the frame size, for a drawout device.
- Use EcoStruxure Power Commission software (EPC)
- Once connected, click the Device Check Up box, click the Maintenance tab, go to Last Maintenance Details box and click View History.
- Edit the Date, Company in charge, maintenance operator name.
- Enter password and save data
- The Service LED will now go out.
How to enable/disable maintenance alarms:
- Disabling maintenance alarms is not recommended unless you have a robust maintenance schedule that matches the alarm frequency.
- Use EPC software
- Once connected click the configure box, click the alarms tab, then click Maintenance on the left
- Scroll down to the basic, standard or manufacturer alarm to enable/disable
發佈於: 施耐德電機Taiwan